Take-apart model · one liquid-cooled GPU tray

Why AI needs water

Eight GPUs turn electricity into heat. Water carries it away. Move the load and watch every number follow.

3,461×

litres of air needed to carry the heat of 1 litre of water, at the same temperature rise

GPU load25%
Heat per GPU0 W
Tray heat0 kW
Pump speed0 %
Coolant flow0 L/min
Coolant in0 °C
Coolant out0 °C
Rise ΔT0 K
GPU case, est.0 °C
Air to do the same job0 m³/s
Facility water out0 °C
If a tower evaporates it0 L/h

Q = ṁ · cp · ΔT

Assumed, not measured: 1,000 W per GPU at full load, 150 W idle, 8 GPUs, 30 °C coolant in, 10 K rise at full load, pump 30% at idle, facility water 25 °C, cold plate 0.02 K/W. Water cp 4,186 J/(kg·K). Air cp 1,005 J/(kg·K) at 1.2 kg/m³.